Specifications |
| Manufacturer |
UNI-T |
| Meter type |
insulation resistance meter |
| Type of display used |
LCD (9999) 19mm |
| Bargraph |
29 segm. |
| Test voltage |
1000VDC (for 2M...10GΩ range), 100VDC (for 0,1M...500MΩ range), 250VDC (for 0,5M...1,99GΩ range), 500VDC (for 1M...3,99GΩ range) |
| Insulation resistance measuring ranges |
0,1M...100M/500M/1000M/2G/4G/10GΩ |
| Insulation resistance measuring accuracy |
(3% + 5 digits) |
| AC voltage measuring range |
1...30/750V |
| AC voltage measuring accuracy |
(2% + 3 digits) |
| DC voltage measuring range |
1...30/600V |
| DC voltage measuring accuracy |
(2% + 5 digits) |
| Continuity test |
acoustic signal for R<30Ω |
| Pollution degree |
2 |
| Body dimensions |
202 x 155 x 94mm |
| Weight with battery |
2kg |
| Power supply |
8 batteries 1,5V LR14 |
| Conform to the norm |
EN61010 1000V CAT II, EN61010 600V CAT III |
| |
Measuring instrument features:
- 4 methods of insulation resistance measurement: continuous, during determined time, polarization index and comparative measurement
- autoranging
- automatic power-off
- large, backlit LCD with bargraph
- 18 measurements memory
- continuity test with buzzer
- overload protection
- low battery indicator
|
Standard equipment:
- crocodile clips
- test leads
- plastic case
|
|